Emergency Fire P/P Regulation



  1. It would be fitted/located outside of E/R.
  2. It will have a connection from em'cy fire supply.
  3. It would be motor driven or engine driven.
  4. It should be capable of supply two jets of water at a time, of 12.5 mm dia and throw of 12 meter with a pressure of 2.1 bar.
  5. Should have 40 % capacity of the main fire p/p.
  6. Should not less than 25 m3/hr.
  7. Suction lift not more than 4.5 meters (for positive displacement p/p)
Suction lift not more than 2.0 meters (for centrifugal p/p with priming unit.)
  1. Can be started 6 times – 30 min.
                        2 times – 10 min.
  1. Fuel tank capacity full load min – 3 hours.